Wire Size Voltage Drop Calculator – NEC AWG Sizing Tool

Wire Size Voltage Drop Calculator

Estimate conductor voltage drop with Vdrop = 2 x length x current x resistance / 1000 for single-phase, or the 1.732 factor for three-phase. Check the percent drop against NEC targets of 3 percent for a branch and 5 percent overall, see the voltage at the load end, and find the smallest AWG copper or aluminum conductor that keeps you inside your target.

🎯Real Circuit Presets

🔌Circuit and Conductor Inputs

Nominal supply voltage, for example 120, 208, 240, or 480.

Single-phase doubles the run; three-phase uses 1.732.

Aluminum has roughly 1.6 times the resistance of copper.

Resistance per 1000 ft is pulled from the NEC-style table.

Distance from source to load, one direction only.

Meters are converted to feet internally (1 m = 3.281 ft).

Continuous or design current the circuit carries.

NEC recommends 3 percent branch and 5 percent total.

Used only when the target above is set to Custom.

Voltage drop 0 V volts lost in the conductor
Percent drop 0 % end voltage shown below
Result vs target - against your target
Recommended min size - smallest AWG that passes

🔱Formula Snapshot

21-phase factor
1.7323-phase factor
3%branch target
5%total target

📋Conductor Resistance (Ohm per 1000 ft)

Wire SizeCopper Ohm/kftAluminum Ohm/kftNotes
14 AWG3.074.91Small branch
12 AWG1.933.09Common outlet
10 AWG1.211.94Dryer, small AC
8 AWG0.7641.22Range, welder
6 AWG0.4910.786Sub-feed 55A
4 AWG0.3080.493Feeder 70A
2 AWG0.1940.310Feeder 95A
1/0 AWG0.1220.195Service 125A
2/0 AWG0.09670.155Service 145A
4/0 AWG0.06080.0973Service 195A

⚡Copper Ampacity by Temperature Rating

Wire SizeAmps at 60CAmps at 75CTypical Breaker
14 AWG15 A20 A15 A
12 AWG20 A25 A20 A
10 AWG30 A35 A30 A
8 AWG40 A50 A40 A
6 AWG55 A65 A50 A
4 AWG70 A85 A70 A
2 AWG95 A115 A100 A
1/0 AWG125 A150 A125 A
3/0 AWG165 A200 A200 A
4/0 AWG195 A230 A200 A

📏NEC Recommended Maximum Voltage Drop

Circuit PartRecommended MaxOn 120 VOn 240 V
Branch circuit3 percent3.6 V7.2 V
Feeder only3 percent3.6 V7.2 V
Feeder plus branch5 percent6.0 V12.0 V
Sensitive electronics2 percent2.4 V4.8 V
Motor at startUnder 10 percent12.0 V24.0 V
Long outdoor run3 percent3.6 V7.2 V

🗃Wire Size Comparison Grid

Wire SizeArea kcmilArea mm2Copper Ohm/kftAmpacity 75CTypical Use
14 AWG4.112.083.0720 ALighting circuits
12 AWG6.533.311.9325 AReceptacles
10 AWG10.45.261.2135 AWater heater
8 AWG16.58.370.76450 ARange, dryer
6 AWG26.213.30.49165 ASub-panel feed
4 AWG41.721.20.30885 ASmall feeder
2 AWG66.433.60.194115 AService feeder
1/0 AWG105.653.50.122150 AMain service
2/0 AWG133.167.40.0967175 ALarge service
4/0 AWG211.6107.20.0608230 A200A service

⚙Formula Breakdown

Vdrop single-phaseVoltage drop equals 2 times one-way length times current times resistance per foot. Vdrop = 2 x L x I x (R / 1000), where R is ohms per 1000 ft.
Vdrop three-phaseFor three-phase the constant 2 is replaced by 1.732 (the square root of 3), so Vdrop = 1.732 x L x I x (R / 1000).
Percent dropDivide the voltage drop by the system voltage and multiply by 100. pctDrop = Vdrop / V x 100.
End voltageThe voltage available at the load is the source voltage minus the drop. endVoltage = V - Vdrop.
Pass or failThe run passes when pctDrop is less than or equal to your target, for example 3 percent for a branch circuit.
Recommended sizeThe tool scans the AWG table and reports the smallest conductor whose percent drop still stays at or under the target.

💡Wiring Design Tips

Watch runs over 100 ft: Voltage drop climbs with distance, so a 20 A load on 12 AWG that is fine at 50 ft can exceed 3 percent past about 100 ft. On long pulls, bumping from 12 AWG to 10 AWG or from 10 AWG to 8 AWG usually brings the drop back under target and keeps motors and heaters running at full output.
Aluminum needs one size up: Aluminum carries about 1.6 times the resistance of copper for the same AWG, so if a copper 6 AWG passes at 3 percent, an aluminum conductor often needs to be 4 AWG to match. Always keep the load current comfortably below the ampacity in the 75C column and treat voltage drop as a separate check.

Now maybe you’ve been noticing how dim the lights are these days, or how the air conditioner drops voltage on the whole house. You’re experiencing voltage drop in action. It’s annoying, it’s invisible, and thankfully, we can plan for it and make it go away.

The wire size voltage drop calculator does all the hard work for us here. It makes complex math easy and gives a simple pass/fail decision at the end.

How to Use a Voltage Drop Calculator

All wires has some amount of resistance. Resistance uses voltage before it gets to the item you want it powering. At short runs, you hardly even notice. Stretch the run to a subpanel or a shed, though, and those missing volts becomes very important. It’s simple, just Physics at work. While both copper and aluminum wires does conduct electricity well, they’re not perfect. There’s a specific rating for how much each size of wire resists electricity, measured in ohms per thousand feet. The thinner the wire, the greater amount of resistance; the higher the resistance, the more voltage that’s wasted along the way as heat. This means that a large six AWG cable will drop less voltage then a small skinny twelve AWG cable carrying equal current.

The calculator simply takes that into account with standard formula automatically, no need to remember the coefficients. On single-phase circuits, the current travels out and then returns, so length is doubled. For three-phase, it multiplies by 1.732. Just select type of phase you want to calculate, and let the tool do the math.

Basically what we’re looking at here are our two main targets from the National Electrical Code
 Three percent for branch circuits and five percent for the entire path (service to load). While it’s not a hard law everywhere, it is a strong recommendation for a good reason. Motors running low on voltage will pull more current as compensation, overheating their windings in the process. Sensitive electronics may simply stop working altogether. By keeping the drop below three percent you’ll ensure your equipment runs efficiently and has a longer life.

The tool tells you instantly whether or not the wire size you have chosen will realy work with your specific set-up. This is where folks get hung up. They choose their wire solely by current capacity. Yep, that twelve AWG wire can handle twenty amps without melting. So what? That run is two hundred feet long. There’ll be a ton of voltage drop. Your lights will dim but the wire won’t melt. To meet requirements of both safety and performance you have to check voltage drop in addition to ampacity. When ampacity looks good but the voltage drop calculator shows a fail, time to upsize the conductor. Sometimes just jumping from twelve AWG to ten AWG will pull those percentages into an acceptable range.

Material also matters. For the same size, copper has roughly 60 percent lower resistance than aluminum. (Aluminum is also less expensive and lighter.) You won’t be able to replace them one-for-one without accounting for that fact. If you choose aluminum from the dropdown, the calculator will do this automatically for you. It’s a simple toggle, but it would of saved you some costly mistakes out in the field.

Keep in mind that heat ratings are not the same as voltage drop. Your wire needs to be large enough to transport current safely, and then large enough to reduce loss even more. Whichever is the greater requirement dictate your wire size. This is meant to be used in conjunction with a good engineer, NOT AS A replacement for one! Local amendments, temperature corrections, and conduit fill factors affects real-world installs. However, this is a great starting point for most residential or light commercial applications.

This will show you why larger wire should of been used for longer runs. It helps you avoid those red-faced “I’ve got a new piece of equipment, but it’s not performing well” situations caused by insufficient power at the start of the install. You’ll save yourself some headaches down the road by doing it right up front.

Wire Size Voltage Drop Calculator – NEC AWG Sizing Tool